| Ozone Protection - EAc4 |
|
Implementation |
HVAC&R Equipment with No HCFCs
- Requirement achieved through EAp3
Ozone-depletion and global-warming potentials of refrigerants |
Refrigerant |
ODP |
GWP |
Building Applications |
Chlorofluorocarbons |
CFC-11 |
1.0 |
4,680 |
Centrifugal Chillers |
CFC-12 |
1.0 |
10,720 |
Refrigerators, Chillers |
CFC-114 |
0.94 |
9,800 |
Centrifugal Chillers |
CFC-500 |
0.605 |
7,900 |
Centrifugal Chillers |
CFC-502 |
0.221 |
4,600 |
Low-Temperature Refrigeration |
Hydrochlorofluorocarbons |
HCFC-22 |
0.04 |
1,780 |
Air Conditioning, Chillers |
HCFC-123 |
0.02 |
76 |
CFC-11 Replacement |
Hydrofluorocarbons |
HFC-23 |
< 4 x 10-4 |
12,240 |
Ultra-Low-Temperature Refrigeration |
HFC-134a |
< 1.5 x 10-5 |
1,320 |
CFC-12 or HCFC-22 Replacement |
HFC-245fa |
~ 10-5 |
1,020 |
Insulation Agent, Centrifugal Chillers |
HFC-404A |
~ 10-5 |
3,900 |
Low-Temperature Refrigeration |
HFC-407C |
~ 10-5 |
1,700 |
HCFC-22 Replacement |
HFC-410A |
< 2 x 10-5 |
1,890 |
Air Conditioning |
HFC-507A |
~ 10-5 |
3,900 |
Low-Temperature Refrigeration |
Natural Refrigerants |
CO2 |
0 |
1.0 |
|
NH3 |
0 |
0 |
|
Propane |
0 |
3 |
|
|
|