Designed to be an economical choice for variable air volume and room control, the MACH‑ProAir™ is a fully programmable BACnet Building Controller (B‑BC) with an optional onboard actuator and flow sensor. Available with numerous standard applications, the MACH‑ProAir communicates over MS/TP and accommodates several input/output configurations to suit your needs.
Dynamic Database
Protocol
Motor Control
Engineered Enhancements
Programs
Inputs
Outputs
Values
Loops
Single-point Trend Logs
Multipoint Trend Logs
Runtime Report
System Groups
Schedules
Calendars
Arrays
Tables
Custom Units
SMART-Net Port
64 Net Ins
32 Net Outs
Warranty
Typical Object Configuration
There are physical limitations to the number of inputs, outputs, and SMART-Sensors that can be connected to a MACH-ProAir controller. For other object types, a maximum number of 128 objects of a single type can be created. The total number of objects (including inputs, outputs, and SMART-Sensors) is limited to 160, and is also limited by the onboard memory. The table below details typical databases that fit in all models.
Variables | Loops | Schedules | Calendars | Tables* | Groups | Multipoint Trend** | Runtime* | Arrays | Program | SMART-Sensor |
64 | 8 | 4 | 2 | 4 | 4 | 10 | 128 | 4 | 16 | 4 |
* Runtime Reports and Tables are not counted in the 160 object limit. Inputs and outputs are counted in the 160 object limit.
** Trends are configured to store 128 samples.
Processor and Memory
Supply Voltages
Communication Options
Universal Inputs
Velocity Sensor
Flow Pickup
Universal Outputs
Solid-State Relay Outputs
Wiring Terminal
Actuator
Dimensions
Base model:
19.9 cm L x 10.1 cm W x 7.3 cm H
(7 13/16" L x 3 15/16" W x 2 7/8" H).
With actuator:
22.7 cm L x 10.1 cm W x 7.7 cm H
(8 15/16" L x 3 15/16" W x 3" H).
With MPA-C:
22.7 cm L x 15 cm W x 7.7 cm H
(8 15/16" L x 5 7/8" W x 3" H).
Mount Hardware Included
Weight
Ambient Limits
Enclosure
Certifications